Hi,
I'm a new user in OSI Soft World.
I have a problem in PE configuration. In my system PE tags are calculated perfecty if PINODE and PISERVER are attive. If i disconnect PInode from network , data are buffered. when a reconnect the PINODE in nthe network the data are sent to pISERVER. All tags are updated except the PE tags. I configure this PE tags with shutdown attribute =0 but doesn't work. somone can help me?

i too agree. PE equations
Tue, 03/16/2010 - 02:07 — inform2prabhati too agree. PE equations are on PIServer and need to recalculate if there is a gap.
PE (Performance Equation)
Fri, 03/12/2010 - 19:12 — neuhach1PE (Performance Equation) tags are calculated on the PI server. I think the PE scheduler cannot handle buffered tag values. Maybe you can use the PI Recalculator to recalculate the PE tags. However, you should configure Shutdown=1 to insert the Shutdown marker when the PI server is not running.